SCARED - WARN - ALARM - EXTINGUISH
- Save yourself and others around you, but don't take too many risks yourself
- Warn others who may be in danger
- Alert the emergency services by calling 112
- Extinguish the fire if possible
Evacuation alarm in case of fire
In corridors, public and technical areas, there are smoke detectors that automatically trigger an evacuation alarm in the event of fire smoke. Alarm is indicated by bell and flash light on the plane where smoke is indicated. Limit the source of the fire by closing doors. A triggered alarm is connected as a priority alarm to Akademiska Hus' emergency response officer who, after checking the alarm, contacts the fire service for a call.
In the event of a fire, call 112 as the evacuation alarm is not directly forwarded to the Rescue Service .
Fire cells
The building is divided into a number of fire cells to prevent fire and smoke from spreading. Each fire cell is delimited by fire-rated walls and doors. In principle, all floors, stairwells, lifts, operating areas and waste rooms have their own fire cells. Doors in fire compartment boundaries can be magnetically suspended in the open position for transport and closed manually with a push button marked "fire door closer". When an evacuation alarm is triggered, the doors close automatically within the alarmed area.
Doors in fire cell boundaries must absolutely not be blocked or set up with wedges or the like!
Escape routes/Collection point
At least two escape routes can be reached from each workplace. The escape routes, which are marked with green, luminous escape signs, must never be blocked. The green signs are always lit and have a battery backup to illuminate even in the event of a power cut.
If the fire alarm is triggered, all personnel must leave the building, close all doors behind them and gather at the assembly point Huvudentrén, Nobels väg 1. The personnel report there to the evacuation receiver. No one may depart from the assembly point until this is done.